Exact manufacturer reference

GEWISS GWD9415

Request current identity, condition, availability, lead-time and delivery review for this catalog reference.

Catalog identity record GEWISS GWD9415 No unverified product photograph is presented as technical evidence.
Model data verified
ManufacturerGEWISS
Part number / MPNGWD9415
Price & lead timeConfirmed during RFQ review; no stale public value shown
Technical statusEvidence requested with RFQ
Source checkedJul 2, 2026

Official model record

MSXE 1250 - MCCB WITH ELECTRONIC RELEASE - LSI - FRONT TERMINALS - 50kA 4P 1250A 690V

Description
Interruttore automatico scatolato
Code
MSXE 1250
No. of poles
4P
Rated current
1250 A
Release
Electronic
ELECTRICAL CHARACTERISTICS
-
MECHANICAL CHARACTERISTICS
-
Standard
IEC/EN 60947-2
Execution
Fixed
Use category
B
DIN rail mounting
No
Rated frequency (Hz)
50 / 60
Can be equipped with motor operator
Yes
Rated operating voltage (Ue)
690 Vac
Compatible interlock
-
Rated impulse withstand voltage (Uimp)
8 kV
Terminals supplied
Front FB Extended
Overvoltage category
IV
Assembly position
Any
Insulation voltage (Ui)
800 V
Upline/downline power supply
Yes
Thermal regulation
0,4 - 0,5 - 0,63 - 0,8 - 0,9 - 0,95 - 1 x In
Electrical life (415Vac)
4.000 cycles
Magnetic regulation
Electronic LSI
Mechanical life
5.000 cycles
Neutral protection
50% - 100% x Ir
Operating temperature
-5°C +65°C
Total power loss
281.24 W
Stocking temperature
-20° +65°
Rated short-circuit current making capacity (Icm)
-
Weight (kg)
25
Rated short-time withstand current for 0,3s (Icw)
15 kA
Width
280 mm
Idn regulation
-
Height
370 mm
DT regulation
-
Depth
120 mm
SERVICE BREAKING CAPACITY (ICU)
-
RATED BREAKING CAPACITIY (ICS)
-
220/240Vac
85 kA, 65 kA

Source: Official GEWISS model product record. Ordering-code suffixes and current manufacturer revisions must still be checked before release.

Sourcing record

Product and identification context

GEWISS GWD9415 is identified by the manufacturer's official product record as “MSXE 1250 - MCCB WITH ELECTRONIC RELEASE - LSI - FRONT TERMINALS - 50kA 4P 1250A 690V”. The official record publishes model-specific fields including Description, Code, No. of poles, Rated current, Release, ELECTRICAL CHARACTERISTICS. Values shown on this page are transcribed from that source and should be checked against the current manufacturer document and the complete ordering code before purchase.

Manufacturer's official product information

Substitution control

Verify before order

  • Rated voltage, current, frequency and number of poles
  • Device function, utilization category and trip or fuse characteristic
  • Terminal type, conductor range and mounting method
  • Breaking capacity, protection rating and coordination requirements
  • Applicable approvals, standards and accessory compatibility

No unverified voltage, pressure, dimension, material or performance value is assigned on this page.